Industrial-grade water body fluoride ion sensor KSA-F-100.0 online. High-precision detection, Pt1000 automated temperature correction, and 5-8pH water sample environment are its features. IP68 high protection, RS-485 (Modbus/RTU) digital output, and 3/4NPT pipe thread immersion are available in the POM corrosion-resistant shell. A popular fluoride ion online detector in drinking water, industrial wastewater, and water environment monitoring, it is easy to use and maintain.
★★★★★
Parameters
| Item | Specification |
|---|---|
| Measuring Range | 0-100.00mg/L |
| Resolution | 0.01mg/L |
| Accuracy | ±10% or ±1mg/L, ±0.5℃ |
| Applicable pH Range | 5-8pH |
| Operating Temperature | 0-50℃ |
| Operating Pressure | <0.2MPa |
| Power Supply | 12-24VDC |
| Signal Output | RS-485(Modbus/RTU) |
| Temperature Compensation | Automatic Temperature Compensation (Pt1000) |
| Calibration Method | Two-point Calibration |
| Mounting Method | Immersion Installation, 3/4NPT Pipe Thread |
| Cable Length | 5m (Other lengths customizable) |
| Power Consumption | 0.2W@12V |
| Housing Material | POM |
| Protection Grade | IP68 |
Why choose KSA-F-100.0 Fluoride ion sensor?
- 0.01mg/L ultra-high resolution, measurement accuracy of ± 10% or ± 1mg/L, high detection accuracy
- Pt1000 automatic temperature compensation, working in a wide temperature range of 0-50 ℃, to counteract the interference of temperature on measurement
- POM corrosion-resistant shell, IP68 waterproof, working pressure<0.2MPa, suitable for complex water quality conditions
- RS-485 (Modbus/RTU) standard output, directly connected to PLC/DCS, supports remote data control
- 3/4NPT pipe thread immersion installation, 5-meter cable can be customized, suitable for multiple installation scenarios
Featured Applications
- Drinking water safety monitoring: online detection of fluoride ion concentration in waterworks and drinking water sources to control core water quality indicators of drinking water
- Industrial wastewater treatment: fluoride ion monitoring of production wastewater in the chemical, electroplating, and metallurgical industries, guiding process regulation to ensure standard discharge
- Natural water environment monitoring: Long term online monitoring of fluoride ions in rivers, lakes, groundwater and other water bodies to grasp changes in water environment quality
- Food and beverage processing: Fluorine ion detection of production process water and ingredient water meets the water quality standards for food and beverage production

Installation and wiring
Installation requirements
- 3/4NPT pipe thread immersion installation, ensuring that the measuring end is completely submerged in the water sample to be measured;
- Avoid strong water flow impact and dead corners of the tank to ensure sufficient contact between the water sample and the sensor;
- Only suitable for 5-8 pH water samples, water sample pretreatment is required if it exceeds the range.
Electrical wiring
- Standard 4-core twisted pair shielded wire, strictly check the wiring sequence before powering on to avoid equipment damage;
- Waterproof and anti-corrosion treatment should be carried out at the connection point, suitable for underwater, humid outdoor and other scenarios;
- Ensure stable power supply at 12-24VDC to prevent data drift caused by voltage fluctuations.
Maintenance and Calibration
Routine maintenance
- Regularly clean the measuring end with a soft bristled brush and distilled water to avoid scratching with hard objects, and use it after drying;
- Rinse the measuring end with distilled water before long-term discontinuation, dry it and store it in a dry and room temperature environment;
- Check the sealing of cable joints and reseal them promptly if they become loose or leak water.
Calibration operation
- Using the two-point calibration method, prepare two sets of fluoride ion standard solutions with low, medium, and high concentrations within the range of 0-1000mg/L;
- After rinsing the measuring end with distilled water, immerse it in two sets of standard solutions, and send calibration instructions to complete zero and slope calibration after the values stabilize;
- Calibrate once every 1-3 months under normal operating conditions, and shorten the calibration cycle for high pollution and high impurity water samples.
Technical Support
Top 6 Industrial Gas Analyzers Manufacturers 2025
6 Best Industrial Gas Detector Manufacturers in the World
9 Best Portable Carbon Dioxide Detector 2025 – Complete Buying Guide
Top 7 portable combustion analyzer Tested
The KSA-F-100.0 online fluoride ion sensor is accurate, doesn’t rust, and is simple to use. It can meet all of your industrial-grade fluoride ion online monitoring demands and comes with full quality assurance and technical support. There is enough supply, and it may be changed to fit your needs. Please feel free to ask for help in choosing and buying in bulk!
Request a Quote
.png)